Reference:
FHSD8015-09
Smoke detector by suction LaserSense Micra 10 with laser camera for early detection. Dynamic 0,0015% to 25% range of darkening/metre. 1 piping input up to 50 m. maximum. ClassiFire algorithm for dynamic adjustment of functional parameters (dirt, environment, etc). LDD 3D3 technology, for dirt adjustments in laser camera. 4 alarm levels (Aux, Pre-alarm, Alarm 1 y Alarm 2). Maximum number of sampling points 10 in class C, 6 in class B y 2 in class A. 2 relay outputs (Alarm and breakout). Requires 24V power supply (350mA). Optional aditional Input and output card. Measures: 1145x220x85mm. Certificates: CE and CPR (EN54 part 20).